The records

Every number on this site comes from EAGLE-I, the outage records kept by Oak Ridge National Laboratory for the US Department of Energy. Every 15 minutes, EAGLE-I reads the outage maps that utilities publish and records how many customers are without power in each county. We use the published 2014–2025 records (Brelsford et al., Scientific Data 11, 271, 2024; figshare, CC BY 4.0).

A "customer" is an electric account, usually a home or a business, not a person.

What counts as an outage

We count an outage when at least 1 in 100 of a county's customers (and at least 10) are without power. Readings less than an hour apart are joined into one outage, and so are outages split by a gap in the records of up to 6 hours, because a gap usually means a missed reading, not the power coming back.

How long an outage lasted

We measure an outage by the time from its start until 9 in 10 of the customers who lost power had it back. The last few customers often wait much longer, so your own outage may have been longer than this figure, or much shorter.

Averages

Coverage grew from about 2,150 counties in 2014 to over 3,000 by 2022. Averages ("big outages a year", "hours without power") use 2018–2025, when nearly every county was covered. Lists of outages use every year.

"Hours without power" adds up every customer's hours without power during the big outages in a year and divides by the number of customers in the county. Small outages (under 1 in 100 customers) are left out, so everyday outages on a single street don't show here.

For the number of customers we take the larger of the two counts in the records (the dataset's modeled count and its 2024 count), because the modeled count is far too low for some counties.

Very long readings

Some readings last for weeks or months, usually a handful of customers "out" on a utility map that was never updated. We leave readings longer than 30 days, and readings showing far more customers out than the county has (over 1.5 times), out of the totals, and list them on the county page.

What these numbers can't tell you

These are counts for a whole county. A county can have a big outage that never reached your street, and a fallen tree can leave your street dark when the county looks fine. Times are converted to each state's main time zone, so a date can be off by a day near midnight.

Backup sizing

To size backup, we assume about 2 kWh a day: a full-size fridge (most use about 1 to 2 kWh a day), phone charging and LED lights, plus the power lost in a battery and its inverter. Freezers, medical devices, heat and air conditioning need more. A closed fridge keeps food safe for about 4 hours without power, a full freezer about 48 hours (USDA). The fridge lookup uses the ENERGY STAR list of certified refrigerators (US Environmental Protection Agency); in that list the typical full-size model uses about 460 kWh a year, about 1.25 kWh a day.